The battery testing and maintenance system allows the technicals to perform battery voltage measurements, capacity testing and discharge test.
The ISA BTS 200 MKII battery test assembly is designed to perform different types of tests required in power generation plants, substations to ensure power to critical elements of the network such as power relays, circuit breakers.
The BTS 200 MKII performs the most reliable test for the determination of the capacity of the battery, executing automatic discharge tests being able to reach currents of up to 1300A by expanding through external loads.
On its backlit screen you can read the following parameters:
Maximum discharging current with BTS 200 MKII. |
|
BATTERY NOMINAL VOLTAGE | MAX CURRENT DISCHARGED |
240 V | 70A |
220 V | 70 A |
140 V | 130 A |
110 V | 130 A |
48 V | 130 A |
24 V | 130 A |
Testing features |
|
Load patterns | • Constant discharge current • Constant power • Current profile (up to 20 steps) • Power profile •Control Manual |
Measurement of the Discharging Current | • Range: 0 - 130 A • Display: 0 - 130 A (0 - 1300 A with external loads) • Accuracy: ± 1 % of the value, ± 0.2 % of the range. The dicharging activity can be stopped and started again later from the same level. |
External Current Measurements |
Testing can be carried out without disconnecting the battery.Using the optional current clamp, BTS 200 MKII measures the total current while regulating it at a constant level.The external current measurement can be performed also by shunt connection. |
Other features |
|
External Current Measurement with Clamp or Shunt | 1V - 100mV ( 100 mOhm - 0.1 mOhm) with 10A - 1000A |
Setting of the Minimum Voltage Threshold | From 20V to 270V with step of: ± 1 V |
Maximum Float Voltage | Up to 270V |
Measurement of the Battery Voltage | • Range: 0 - 300 V • Display: 0 - 99.9 or 0 - 999 V; auto ranging • Accuracy: ± 1 % of the range, ± 0.2 % of the range |
Setting of the Maximum Testing TimeFrom 0 to 15 hours or infinite (without recording)Internal Memory8 discharging sequences; non volatile internal memory | |
Automatic Stop Functions | • Minimum voltage threshold • Maximum capacity • Time out (Max. 9h.59’) • System alarm |