2, 3 and 4 point testing with selectable 25V or 50V output. Easy to use one button operation. Robust IP54 rated instrument
Megger's DET4TD2 is an enhanced earth loop tester that is capable of perform 2, 3 and 4 point testing with selectable 25V or 50V output.
Suitable for use both indoors and outdoors thanks to IP54 rating (protection from dust and water jets) the Megger DET4TD2 is easy to connect up, and tests are easily chosen and initiated by use of the large rotary dial and test button. There's also a button built into the front of the instrument for switching between 25 and 50V modes.
This earth tester will also automatically evaluate and display the connection and condition of any connected P and C spikes, showcasing the results on the built-in LCD screen. You can also use the DET4TD2 to get an accurate measurement of ground voltage thanks to a built in voltmeter, and this instrument is also able to measure earth voltages up 100V, as well as resistance measurements from 0.01Ω to 20kΩ (with resistance accuracy of 2%±3 digits).
The Megger DET4TD2 is a non-rechargeable instrument and runs on 8 x AA batteries. Its sister tester, the DET4TR2, is rechargeable.
This product complies with the requirements of IEC61010-1 100V CAT IV between terminal pairs, provided a leadset with this rating is used. The DET4TD2 is also in compliance with KEMA K85B and EN61557 "Electrical safety in low voltage distribution systems up to 1000V a.c and 1500V d.c - Equipment for testing measuring or monitoring of protective measures".
Megger DET4TR2 Technical Specifications |
|
Index Protection | IP54 |
C Spike, P Stake and Noise Check | Automatic |
Noise Rejection | 40V Peak to Peak |
2-Wire, 3-Wire, 4-Wire Tests | Yes, with no shorting links required |
Instrument Output | Voltage: ± 25V or ± 50V at 128Hz Current: 4.5mA or 0.45mA |
Resistance Range | 0.01Ω to 20kΩ |
Earth Voltage Range | 0 to 100V |
Resistance Accuracy | 2P measurements: 2% ±3 digits 3P measurements: 2% ±3 digits 4P measurements: 2% ±3 digits |
Maximum Probe Resistance | Rp limit: 100 kΩ (50 V output voltage) Rc limit: 100 kΩ (50 V output voltage) Limits reduced to 50 kΩ for 25 V output voltage Limits reduced to 5 kΩ for 0.01 Ω resolution |
Ground Voltage Range | 0 to 100V AC |
Ground Voltage Accuracy | 2% ± 2V |
Display | 3 1/2 high contrast liquid cristal |
Battery Type | 8 x AA (LR6) NiMH Rechargeable Cells |
Operating Temperature Range | -15 to +55 ºC / 5 ºF to 131 ºF |
Storage Temperature Range | -40 to +70ºC / -40 ºF to 158 ºF |
Safety | Complies with the requirements of IEC61010-1
100 V CAT IV between terminal pairs.* * The CAT IV 100 V is dependant on the use of a leadset of at least this rating, for example the optional two wire leadset part number 1001-858. |
EMC | In accordance with IEC61326-1 |
Standards Compliance | Complies with the requirements of KEMA K85B.
Complies with the following parts of EN61557, “Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. - Equipment for testing, measuring or monitoring of protective measures”. Part 1 - General requirements Part 5 - Resistance to earth |
Dimensions | 203 x 148 x 78 mm (8 x 5.8 x 3 inches) |
Weight | 1 kg (2.2lb) |
Contact us by filling out this form: